Simply select your desired temperature or humidity stop point, the setpoints for the Day / Night, and the TSH-1 will control that device’s variable speed or opening % based on the stop point and Day / Night setpoints.
There is no need to provide power supply for the TSH-1 unit. It can be connected to the Hydro-X with our standard RJ12 data cable.
The LCD screen of the TSH-1 will display the setpoint for temperature or humidity, and the actual current temperature or humidity level as well as the current % / speed the device is operating at.
The TSH-1 can control any device that uses a 0-10 vdc signal. In the instructions example we will be referring to using it to control a fan.
The TSH-1 will control the temperature or humidity by adjusting the variable speed fan or vents or other devices that accept a 0-10VDC ANALOG SIGNAL.
The horizontal Y coordinate represents the fan speed % / output voltage from 0-10vdc.
There are three settings within the TSH-1 module to be set by the user.
Day & Night idle speeds: (Minimum Output) When the current measured temperature or humidity increases above the stop point, but remains below the setpoint, the TSH-1 unit will operate the fan at the idle speed setting.
There are also two settings within the Hydro-x controller to be set by the user.
Temperature/Humidity setpoint: The user will select the Day and Night setpoint within the Hydro-x settings for the TSH-1 module. The setpoint works with the Deadband setting within the Hydro-x to determine the range of speed control. The setpoint is where the TSH-1 will begin to modulate the speed of the fan being controlled.
Deadband: The Deadband setting is set on the Hydro-x. The difference between the set point and the full speed point is the Deadband setting. When the current measured temperature or humidity is above the setpoint selected on the Hydro-x, the fan speed will change proportionally with temperature/humidity. If the temperature/humidity increases, the TSH-1 unit will increase the fan speed by increasing the voltage output towards the 10v limit. If the temperature/humidity decrease, the TSH-1 unit will decrease the fan speed by reducing the voltage down towards to 0v limit.
Full speed point:The full speed point is the setting that combines the user setpoint, with the Deadband setting. In this example, if the user setpoint is 78’F and the Deadband is 4’F, the fan will operate at full speed when the temperature goes above 82’F (10v output from the TSH-1). When the current measured temperature/humidity is at or above the full speed point, the TSH-1 unit will operate the fan at maximum speed.
When the temperature/humidity goes back below the Full speed point, the TSH-1 will again start to modulate the speed output going to the fan.
NOTE: Make sure to insert the positive wire and negative wire of signal cable of the device you are controlling into the positive terminal and negative terminal correctly
When the LCD screen show “Please press Addressing Key”, press the Addressing button on the TSH-1 unit so that the Hydro-X will assign an address such as T1/H1 to TSH-1 unit accordingly. The LCD screen of Hydro-X will display “Station T1/H1 has been added”. Please note T1/H1 may not be the actual address, it can be T2/H2 depending on the connection sequence. The first one is marked as T1/H1, the second one as T2/H2.
To change settings: Press the Menu button to set the minimum idle speed (output) for Day & Night mode and the Stop At point. Press the UP or DOWN button, the digits will be flashing. Then use the UP or DOWN button again to change settings. Press the ENTER button to enter the setting.
When you press Menu once, the LCD screen will display:“Day Min Output xx%”.
When you press Menu twice, the LCD screen will display: “Night Min Output xx%”.
When you press Menu a third time, the LCD screen will display:“Stop At xx%”.
NOTE: Make sure the file name of the firmware upgrade reads: “tsh1_update.hex”
Insert the card into the slot at the bottom of the TSH-1 and press and hold the “Addressing” button while re-connecting the RJ12 cable. The upgrade process will be done automatically
b ) If there are any defects of the TSH-1, TrolMaster will repair or replace using new or reconditioned products within three-years from the original date of purchase. For service, contact TrolMaster tech support for instructions, have the original sale receipt ready.
c ) DO NOT attempt to open the enclosure to prevent electric shock, and voiding of the warranty